How Power Utilities Can Protect Pole Grounds from Cathodic Protection Interference
Where electrical utilities power pipeline stations, tank farms or other facilities that are cathodically protected (CP), both the utility and the facility operators need to understand the potential impact that electrical bonding between their grounding systems can have on their infrastructure.
Most pipeline and storage tank facility operators are keenly aware of the influence of electrical bonds between their facility and the electrical utility – without proper DC isolation from the utility grounding system, the facility’s CP system will lose current to the utility grounds, ultimately compromising the corrosion protection of the facility’s assets [Ref. “DC Decoupling from Utility Grounding Systems”]. However, utility operators often overlook how stray cathodic protection current can affect their grounding system.
CP Interference Can Damage the Utility’s Grounding System
Figure 1 illustrates a basic cathodically-protected pipeline station with the red arrows indicating DC current flowing from the CP system’s rectifier. The majority of the CP current flows to the pipeline, but some of this current will also flow through nearby grounding systems that are electrically bonded to the pipeline, including that of the utility, to return to the rectifier.
![]() |
|
Figure 1. Cathodic Protection interaction with power utility grounding system |
High levels of cathodic protection current pickup at the utility’s grounding electrodes are known to cause formation of calcareous deposits on the electrode which significantly increase the resistance of the primary grounding system. Figure 2 shows an example of such a deposit that has formed on the neutral grounding electrode of a utility pole.
![]() |
|
Figure 2. Calcareous deposit formation on a utility grounding system due to cathodic protection interference. Photo courtesy of Enbridge Inc. |
These deposits can form over months or years depending on the mineral composition and moisture levels of the surrounding soil and on the degree of CP interference. But since the deposits are below grade and unseen, detection requires frequent ground resistance testing and possibly excavation, both of which can be costly.
The increased ground resistance caused by these deposits can lead to less effective fault and lightning current dissipation and reduce the ability of the utility circuit protection system to clear a fault. This can result in high voltage gradients on and near the pole, which present a safety risk to the public and workers and expose nearby equipment to higher voltage stress.
How Can Utilities Prevent CP Interference?
The most practical method of preventing these calcareous deposits from forming is to eliminate the bond between the cathodic protection system and the utility grounding system. However, a bond between primary and secondary circuits is required by most electrical codes (i.e., the National Electrical Safety Code in the US) and cannot simply be eliminated. DC decouplers are a proven safe and effective solution for isolating utility grounding systems from cathodic protection current while maintaining the safety bond. Hundreds of Dairyland decouplers are installed every year to solve this problem.
Often, the most simple and economical method for isolating the utility from CP is to install a single decoupler at the transformer that feeds power to the facility – typically between the primary and secondary neutrals as shown in figures 3 and 4. The fault current rating of the decoupler is set to that of the primary circuit, which is known by the utility, and allows for a decoupler with a much lower fault rating than if installed in the secondary circuit.
![]() |
|
Figure 3. Decoupler installed between primary and secondary circuits |
![]() |
|
Figure 4. Decoupler installation at a single-phase pole-mounted transformer. |
Alternatively, the utility can work with the facility operator to install decouplers within the facility. This method often requires multiple decouplers and can be more complex than installation at the transformer. But the facility operator may prefer to install the decoupler(s) within their facility either because, in many cases, it allows their CP system to operate more efficiently, or they simply want to have control over the installation.
Within the facility, two decoupler installation techniques are commonly used to isolate CP from the utility:
- Isolate individual electrical equipment circuits. A decoupler is installed in series in the electrical grounds of any electrical equipment bonded to cathodic protection, thus preventing CP current in the soil from being picked up by the utility ground and returning to the rectifier via the equipment ground. In this case, the decoupler fault current rating is set by the individual circuit rating. Several decouplers are often required depending on the size and complexity of the station.
- Isolate the entire facility at the main service panel. A single decoupler is installed between the neutral bus and the ground bus at the facility’s main service panel. The decoupler fault current rating is set by the transformer secondary circuit rating.
Dairyland’s Transformer Fault Current Calculator can be used to estimate the fault current on the secondary and the recommended decoupler to be used for this installation.
Because of the voltage difference between the primary and secondary circuits, the required decoupler fault current rating will be much greater in this case than if installed at the transformer.
It should be noted that though this method is safe and effective, it is not explicitly allowed in the US National Electrical Code.
What Decoupler Installation is the Best Approach?
The most simple and economical method for isolating a facility’s CP system from the power utility is to install a single decoupler at the transformer between the primary and secondary neutral and/or other ground connections between the primary and secondary circuits. A single decoupler with a relatively low fault current rating will completely isolate the two systems.
However, though this approach meets the needs of the utility, assuming no other isolation, it does require that the facility’s CP system be designed to protect the facility’s entire grounding grid in addition to other assets. As a result, facility operators may desire to isolate from within their facility.